Falling header temperature:
Sa_ist ≤ Sa_Soll - hysteresis, parallel mode
all mixers towards "CLOSE".
Sa_ist ≤ Sp_soll
all mixers towards "CLOSE" and all heating circuit pumps as
well as all primary pumps at the mixer modules (for cylinder and
convector heaters) "OFF"
Rising header temperature:
Sa_ist > Sp_soll + 2 K
all mixers towards "CLOSE" and all heating circuit pumps as
well as all primary pumps at the mixer modules (for cylinder and
convector heaters) "ON"
Sa_ist ≤ Sa_Soll - hysteresis, parallel mode + 2 K
no forced output
Sample diagram: Set cylinder temperature = 55 °C
Parameter MI 17 = 10 K
Parameter KM 22 = 5 K
Actual header temperature [K]
Forced actuation
Mixer "CLOSE"
Mixer "CLOSE" and pump "OFF"
Time
Parameters / Function description