KM 50 Test function Parameter KM50 enables the individual control of the relays.
KM50 = 1  Control, mixer circuit pump relay MKP
KM50 = 2 Control, mixer motor relay "OPEN" MM
KM50 = 3 Control, mixer motor relay "CLOSE" MM
KM50 = 4 Control, relay output A1
KM 60 Control deviation Indicates the control deviation = set header temperature - actual
header temperature.
KM 61
Overall modulation level
Indicates the overall modulation level.
No display if system conguration 13 and 4 has been selected.
KM 62 Modulation level,
boilers
a) Modulating boilers, if KM 02 = 3:
Indicates the modulation level or all active boilers.
b) Single stage boilers, if KM 02 = 1:
KM 62 = 0% no boiler active
KM 62 = 100% boiler 1 with address 1 active
If an additional boiler is controlled, the KM 62 always shows 100%.
c) Two-stage boilers, if KM 02 = 2:
KM 62 = 0% no boiler active
KM 62 = 50% stage 1 of boiler with address 1 active
KM 62 = 100% stage 2 of boiler with address 1 active
If an additional boiler/stage is controlled, the KM 62 always
shows 100%.
No display if system conguration 13 and 4 has been selected.